CJX2-D115NS CJX2-D205NS
Main datas
Model(CJX2) | Rated insulation voltage | For distribution circuits | For distribution circuits | ||||||
Rated thermal current | Rated operation current 3p-440V 50/60Hz LL/NL | Rated operation power for AC3 difference in temperature of load rated motor power | |||||||
200V | 380V | 415/440V | |||||||
Kw | hp | Kw | hp | Kw | hp | ||||
D115NS | 1000V | 200A | NL/LL 115/- | 30/- | 40/- | 55/- | 75/- | 60/- | 80/- |
D150NS | 1000V | 250A | NL/LL 150/- | 40/- | 55/- | 75/ | 100/ | 80/ | 110/- |
D170NS | 1000V | 275A | NL/LL 170/- | 45/- | 60/- | 80/- | 110/- | 90/ | 120/- |
D205NS | 1000V | 275A | NL/LL 205/185 | 60/55 | 80/75 | 100/90 | 135/125 | 110/100 | 150/135 |
D2054NS | 1000V | 275A | NL/LL 215/205 | 65/60 | 90/80 | 110/100 | 150/135 | 115/110 | 155/150 |
D245NS | 1000V | 315A | NL/LL 245/- | 70/- | 95/- | 120/- | 160/- | 130/- | 175/- |
D2454NS | 1000V | 315A | NL/LL 245/225 | 70/68 | 95/90 | 120/110 | 160/150 | 130/120 | 175/160 |
D300NS | 1000V | 400A | NL/LL 300/- | 85/- | 115/- | 150/- | 200/- | 160/- | 215/- |
D3004NS | 1000V | 400A | NL/LL 320/300 | 90/85 | 125/115 | 160/150 | 215/200 | 170/160 | 230/215 |
D410NS | 1000V | 500A | NL/LL 410/- | 110/- | 150/- | 210/- | 280/- | 225/- | 305/- |
D4104NS | 1000V | 500A | NL/LL 440/410 | 120/110 | 160/150 | 220/210 | 300/280 | 235/225 | 340/305 |
D475NS | 1000V | 700A | NL/LL 475/- | 145/- | 195/- | 250/- | 335/- | 270/- | 360/- |
D4754NS | 1000V | 700A | NL/LL 500/475 | 150/145 | 200/195 | 260/250 | 350/335 | 285/270 | 385/360 |
D620NS | 1000V | 1000A | NL/LL 620/- | 180/- | 240/- | 330/- | 440/- | 400/- | 530/- |
D6204NS | 1000V | 1000A | NL/LL 700/620 | 210/180 | 280/240 | 370/330 | 495/440 | 425/400 | 570/530 |