Product Detail:
Application
Protection against the effects of earth leakage overload and short circuit currents.
2P switching of ph&N,Phase only protected against overloads and short circuits.
In commercial,industrial and domestic electrical distribution systems.Note:must mot be used as the sole means of providing protection against direct contact.
The RCBO incorporates a residual current operated electromagnetic release which operates without any auxiliary source of suppl to open a circuit automatically in the case of an earth leakage fault between phase and earth greater than or equal to In.The RCBO combined MCB&RCCB provides:
Protection against indirect contact
Complementary protection against direct contact
Protection for the installation against in sulation faults
Electrical technical data
Type | V40H |
Number of poles | 1P+N |
Rated Current(In) | 1,2,3,4,6,10,16,20,25,32,40A |
Rated operating current( In) | 30,100,300,500mA |
Rated Voltage(Un) | AC 230(240) V |
Residual operating current scope | 0.5-1 |
Residual current off-time | ≤ 0.3s |
Ultimate short-circuit breaking capacity(Icn) | 6000A |
Endurance | ≥ 4000 |
Terminal protection | IP20 |